狠狠躁夜夜躁人人爽天天5,久久久精品午夜免费不卡,久久亚洲av成人无码电影,永久黄网站色视频免费观看

Products
Your location:home page > Products > Intelligent PDC series

GCS type low-voltage pull-out switch cabinet

Add time:2021-11-24 11:18:26   Number of views:809  

Product introduction

GCS type low-voltage pull-out switch cabinet is suitable for power plant, petroleum, chemical, metallurgy, textile, high-rise building and other industries of power distribution system. As a three-phase AC frequency of 50 (60) Hz, rated working voltage of 380V, 400V, 660V, Low-voltage complete set of distribution devices for power distribution, motor centralized control and reactive power compensation in generator and power supply systems with rated current of 4000A and below.

GCS type low-voltage withdrawl switchgear is designed and developed by two joint design groups according to the requirements of the competent departments of the industry, the majority of electric power users and design units. It conforms to the national conditions, has higher technical performance indicators, can adapt to the development of the electric power market and can compete with the existing introduced products.

Using the environment

● Ambient air temperature is not higher than +40℃, not lower than -5℃. The average temperature within 24 hours shall not be higher than +35℃.

● For indoor use, the altitude of the site shall not exceed 2000m.

● The relative humidity of the surrounding air is not more than 50% at the highest temperature of +40℃. The relative humidity is allowed to be larger at the lower temperature, such as 90% at +20%. It should be taken into account that the influence of condensation may occur occasionally due to the change of temperature.

● When installing the device, the inclination of the vertical plane is not more than 5°, and the whole cabinet column is relatively smooth (in line with GBJ232-82 standard).

● The device should be installed in no violent vibration and impact and not enough to make the electrical components should not be corroded.

● Users have special requirements, can negotiate with the manufacturer to solve.

Ordering instructions

The order contract contains the following contents:

● List of cabinet components;

● The full model of the product includes the main circuit scheme number and auxiliary circuit scheme number;

● Main circuit system combination sequence diagram;

● Auxiliary circuit electrical schematic diagram;

● Circuit voltage, current, time and other setting parameters;

● Other special requirements inconsistent with normal use of the product.

Structural characteristics of

The main frame adopts 8MF type open steel, the two sides of the steel respectively have module 20mm and 100mm φ9.2mm mounting holes, internal installation is flexible and convenient.

The main frame assembly is designed in two ways, full assembly structure and part (side frame and beam) welding structure, for users to choose.

Each functional room of the core device is isolated from each other, and the compartment is divided into functional unit room, bus and cable room. The function of each chamber is relatively independent.

The horizontal main bus is arranged in a horizontal position after the cabinet to enhance the anti-electric bus; It is the basic measure to make the main circuit of the device have high short-circuit strength ability. The design of cable compartment makes the cable up and down are very convenient.

The module of the drawer height is 160mm. It is divided into five size series of 1/2 unit, 1 unit, 1.5 unit, 2 unit and 3 unit. Unit loop rated current 400A and below <> drawer changes only in the height size change, its width, depth size unchanged. The drawers of the same functional unit have a maximum of 11 single drawers or 22 1/2 unit drawers per MCC cabinet.

The drawer panel has the obvious signs of the position such as dividing, closing, testing and pulling out. Drawer units have mechanical interlocking devices.

Main circuit fixed voltage(V)

AC380(400)、(660)

Auxiliary circuit rated voltage(V)

AC220、380(400)     DC110、220

Rated frequency(HZ)

50(60)

Rated insulation voltage(V)

660(1000)

Rated current(A)

The level of bus

≤4000

Vertical busbar(MCC)

1000

Bus-rated peak tolerance current(kA/1s)

50、80

Rated peak withstand current of bus(kA/0.1s)

105、176

Power frequency test voltage(V/1min)

 Main circuit

2500

Service circuit

1760

 Generatrix

Three phase four wire system

A、B、C、PEN

Three phase five wire system

A、B、C、PE、N

 Protection grade

IP3L0、IP4L0

Copyright ? Hebei Bowei Electric Co., LTD. http://www.vmb611.com All Rights Reserved    
HomeTelProduct
久久国产精品成人无码网站| 精品久久久久久无码人妻中文字幕| 中文字幕日韩精品一区二区三区| 国产另类TS人妖一区二区| 精品久久久久久中文字幕大豆网| 国产精品自在拍首页视频8| 久久亚洲精品成人无码| 免费的成年私人影院网站| 亚洲国产精品久久久天堂麻豆宅男| 中文字幕亚洲情99在线| 成人AV专区精品无码国产| 红桃av一区二区三区在线无码av| 国产成人人综合亚洲欧美丁香花| 国语自产少妇精品视频| 亚洲AV无码专区在线观看亚| 国产女人乱人伦精品一区二区| 精品精品国产高清A毛片牛牛| 67194熟妇在线直接进入| 97夜夜澡人人爽人人喊中国片| 成人亚洲性情网站WWW在线观看| 国产乱人伦精品一区二区在线观看| 成人国产精品免费视频| 99热精品毛片全部国产无缓冲| 精品一区二区久久久久久久网站| 亚洲午夜精品久久久久久app| 亚洲av无码乱码在线观看野外| 久久躁狠狠躁夜夜AV| 中文字幕AV人妻一区二区| 国内精品久久久久久久影视麻豆| 亚洲aⅴ无码专区在线观看q| 精品人妻无码区二区三区| 高潮毛片无遮挡高清视频播放| 亚洲成在人网站无码天堂| 国产激情无码一区二区三区| 伊香蕉大综综综合久久啪88| 99久久精品费精品国产一区二| 国产9麻豆剧果冻传媒| 黄色视频在线免费观看| 午夜香吻免费观看视频在线播放| 国产美女久久精品香蕉| 精品亚洲成av人在线观看|